Socket Kits for generators

Four socket kits were designed to be installed on the rear silencer of canopies GV020 to GV200. The external measurements of the panel expressed in mm: 550 width, 435 height, 200 depth. The panel installation will extend the generating set by 200 mm Colour black RAL9005.

The panel is equipped with a top-hinged door to close the switch compartment and a lock with removable key when the door is closed. The total degree of protection is IP44. The socket kit is an integrated accessory to the generating set and cannot be supplied separately.

VERSION DESCRIPTION
NI-00 5-pole 63A 3F+N+E socket protected by a 4-pole circuit breaker, 5-pole 32A 3F+N+E socket protected by a 4-pole circuit breaker, 5-pole 16A 3F+N+E socket protected by a 4-pole circuit breaker, 3-pole 16A 1F+E socket protected by a 2-pole circuit breaker, 16A schuko socket protected by a 2-pole circuit breaker, main switch for 125A sockets with calibrated differential protection;
NI-01 5-pole 32A 3F+N+E socket protected by a 4-pole circuit breaker, 5-pole 16A 3F+N+E socket protected by a 4-pole circuit breaker, 3-pole 16A 1F+E socket protected by a 2-pole circuit breaker, 16A schuko socket protected by a 2-pole circuit breaker, main switch for 63A sockets with 30mA differential protection;
NI-02 5-pole 63A 3F+N+E socket protected by a 4-pole circuit breaker, 5-pole 32A 3F+N+E socket protected by a 4-pole circuit breaker, 5-pole 16A 3F+N+E socket protected by a 4-pole circuit breaker, 3-pole 16A 1F+E socket protected by a 2-pole circuit breaker, 16A schuko socket protected by a 2-pole circuit breaker;
NI-03 NI-03 5-pole 32A 3F+N+E socket protected by a 4-pole circuit breaker, 5-pole 16A 3F+N+E socket protected by a 4-pole circuit breaker, 3-pole 16A 1F+E socket protected by a 2-pole circuit breaker, 16A schuko socket protected by a 2-pole circuit breaker;
The NI-02 and NI-03 panels correspond to NI-00 and NI-01 by socket supply, but they do not have a general differential circuit breaker. In case of earth leakage of the utilities the main differential circuit breaker is triggered (which is compulsory in this case), thereby disconnecting the entire charge. The advantage of the NI-00 and 0 is that one discharge on the sockets will not trigger the main switch on the machine.
CONNECTIONS WITH EXTENDED BARS This is a very useful accessory in cases where the power cables need to be frequently connected or disconnected from the generating set. It allows you to avoid using the screws on the switch (not suitable for frequent use) and connect to the copper bars instead. With the extended connections the cable heads are always attached to the bar leaving the holes free for the cables.